Makes it easy to select a breaker type based on the wire size for the North American market and the short-circuit current of the electrical system.
© 2021, Fuji Electric FA Components & Systems Co.,Ltd. All rights reserved.
back

Model selection
for North America

reset
Diagram
Select a UL489 certified MCCB or ELCB type when applying the AWG (American Wire Gauge) system.

The AWG size resistance corresponds to the 20℃ value in the UL83 Table 15, and the reactance corresponds to the value when IV (or VV) wires are formed into three-wire strands.

The allowable current-carrying capacity indicates the allowable current value for the types (RHW, THHW, THW, THWN, XHHW, USE, ZW: 30°C to 75°C) in NFPA 70 Table 310.15(B)(16).

The short-circuit current is obtained using a simple calculation based on the 3-phase transformer capacity, short-circuit impedance, and the resistance for the AWG size.

Cross reference of transformer capacity [kVA] and short-circuit impedance [%]


[CB1]
* () Indicates the breaking capacity [kA].
[Connection wire]
[CB2]
* () Indicates the breaking capacity [kA].
© 2021, Fuji Electric FA Components & Systems Co.,Ltd. All rights reserved.
close
Breaker selection for wiring protection in North America. CB1 A1 Electric line A2 CB2 Three-phase Transformer capacity Secondary rated voltage Short-circuit impedance X / R ratio Secondary rated current A1-point short-circuit current Rated current MCCB selection type Breaking capacity ELCB selection type Breaking capacity AWG, kcmil size (mm²) Allowable current No. / phase Length A2-point short-circuit current Rated current MCCB selection type Breaking capacity ELCB selection type Breaking capacity ©2021, Fuji Electric FA Components & Systems Co.,Ltd. All rights reserved.